Carbon monoxide detector

A Kidde plug-in carbon monoxide detector

A carbon monoxide detector or CO detector is a device that detects the presence of the carbon monoxide (CO) gas to prevent carbon monoxide poisoning. In the late 1990s, Underwriters Laboratories changed the definition of a single station CO detector with a sound device to carbon monoxide (CO) alarm. This applies to all CO safety alarms that meet UL 2034 standard;[1] however for passive indicators and system devices that meet UL 2075, UL refers to these as carbon monoxide detectors. Most CO detectors use a sensor with a defined, limited lifespan, and will not work indefinitely.

CO is a colorless, tasteless, and odorless gas produced by incomplete combustion of carbon-containing materials. It is often referred to as the "silent killer" because it is virtually undetectable by humans. In a study by Underwriters Laboratories, "Sixty percent of Americans could not identify any potential signs of a CO leak in the home".[2] Elevated levels of CO can be dangerous to humans depending on the amount present and length of exposure. Smaller concentrations can be harmful over longer periods while increasing concentrations require diminishing exposure times to be harmful.[3]

Those living in all-electric homes don’t need CO detectors unless there is an attached garage with a non-electric car, or if a backup generator is used too close to your living quarters during a power outage.[4]

A First Alert smoke and carbon monoxide alarm

CO detectors are designed to measure CO levels over time and sound an alarm before dangerous levels of CO accumulate in an environment, giving people adequate warning to safely ventilate the area or evacuate. Some system-connected detectors also alert a monitoring service that can dispatch emergency services if necessary.

While CO detectors do not serve as smoke detectors and vice versa, combined smoke/CO detectors are also sold.[5] In the home, some common sources of CO include open flames, space heaters, water heaters, blocked chimneys or running a car or grill inside a garage.[6]

Installation

The devices can either be battery-operated or AC-powered (with or without a battery backup). Battery-powered devices advertise a battery lifetime of up to 10 years. The gas sensors in CO alarms have a limited life span, typically two to five years.[7] Newer models are designed to signal a need to be replaced after a set period. CO detectors all have "test" buttons like smoke detectors, but the test buttons only test the battery, electronic circuit, and buzzer, not the alarm’s ability to sense gas.

According to the carbon monoxide guidelines of the National Fire Protection Association, CO detectors should be installed in each sleeping area in a dwelling, and each detector should be located "on the wall, ceiling or other location as specified in the installation instructions that accompany the unit".[8]

CO detectors are available as stand-alone models, or system-connected devices which can be monitored remotely.[9]

Function

The primary purpose of CO detectors is to sound an alarm to warn occupants of an enclosed space of a dangerous level of carbon monoxide. The alarm should sound within 60 minutes if the concentration rises to 70 PPM, within 10 minutes at 150 PPM, in 4 minutes at 400 PPM, and immediately at 500 PPM or greater. The alarm should not sound too quickly, as brief false alarms may prompt users to disable the alarm, leaving them unprotected.[10] Some alarm devices may display the CO level. There are also measuring instruments designed to display CO concentrations down to low, non-dangerous levels, rather than detect and warn of dangerous levels.

Some detectors without UL certification have been found not to sound at the specified threshold, or to sound within seconds.[10]

In some instances, it's worth noting that a red flashing without accompanying sounds could indicate a different condition or simply inform the user about a malfunction.[11]

Wireless home safety devices are available that link carbon monoxide detectors to vibrating pillow pads, strobes, or a remote warning handset.

Several carbon monoxide detection methods are used and documented in industry specifications published by Underwriters Laboratories. Alerting methods include:

  • Audible tones (4 short beeps)
    • Varies between 3,000 and 3,500 Hz depending on brand and model name
    • 105 dB loudness at 3 feet
  • Spoken voice alert
  • Emergency light for illumination

Sensors

Early designs used a chemical detector consisting of a white pad that faded to a brownish or blackish color in the presence of carbon monoxide. Such detectors are cheap but only give a visual warning. As carbon monoxide-related deaths increased during the 1990s, audible alarms became standard.

The alarm points on carbon monoxide detectors are not a simple alarm level (as in smoke detectors) but are a concentration-time function. At lower concentrations, e.g. 100 parts per million (PPM), the detector does not sound an alarm for many tens of minutes. At 400 PPM, the alarm sounds within a few minutes. This concentration-time function is intended to mimic the uptake of carbon monoxide in the body while also preventing false alarms due to brief bursts of carbon monoxide from relatively common sources such as cigarette smoke.

Four types of sensors are available, varying in cost, accuracy, and speed of response.[12] Most detectors do not have replaceable sensors.

Opto-chemical type

The detector consists of a pad of a colored chemical which changes color upon reaction with carbon monoxide. They only provide a qualitative warning of the gas, however. The main advantage of these detectors is that they are the lowest cost, but the downside is that they also offer the lowest level of protection.

One reaction used for carbon monoxide detection is potassium disulfitopalladate (II) catalytic oxidation:

As the reaction progresses, the release of palladium causes the color to change from yellow to brown to black.

Biomimetic type

A biomimetic sensor works in a fashion similar to hemoglobin which darkens in the presence of CO proportional to the amount of carbon monoxide in the surrounding environment. It uses cyclodextrins, a chromophore, and a number of metal salts. This can either be seen directly or connected to an infrared source of photons such as an IR LED and then monitored using a photodiode. Battery lifespan is usually two to three years with conventional alkaline, but a lithium battery will last the life of the product. The biotechnology-based sensors have a useful operational life of six years. These products were the first to enter the mass market, but because they cost more than other sensors they are mostly used in higher-end areas and RVs. The technology has been improved and is the most reliable technology, according to a report from Lawrence Berkeley National Laboratory.[13]

Electrochemical type

Electrochemical Carbon Monoxide sensors. Both sensors and alarms are from different companies.
The metal cylinder with yellow tape on it
The brown cylinder with text on it

The electrochemical detector uses the principle of a fuel cell to generate an electrical current when the gas to be detected undergoes a chemical reaction. The generated current is precisely related to the amount of carbon monoxide in the immediate environment close to the sensor. Essentially, the electrochemical cell consists of a container, two electrodes, connection wires, and an electrolyte, typically sulfuric acid. Carbon monoxide is oxidized at one electrode to carbon dioxide while oxygen is consumed at the other electrode. For carbon monoxide detection, the electrochemical cell has advantages over other technologies in that it has a highly accurate and linear output to carbon monoxide concentration, requires minimal power as it is operated at room temperature, and has a long lifetime, which typically is five years to ten years. This technology has become the dominant technology in the United States and Europe. [citation needed] Test buttons only indicate the operational effectiveness of the battery, circuit, and buzzer. The only way to fully test the operation of a CO alarm using an electrochemical cell is with a known source of calibrated test gas delivered in a shroud to maintain the concentration level for the test period.

Semiconductor type

Thin wires of the semiconductor tin dioxide on an insulating ceramic base provide a sensor monitored by an integrated circuit. This sensing element must be heated to approximately 400 °C for operation. Oxygen increases the resistance of the tin dioxide while carbon monoxide reduces it. The integrated circuit monitors the resistance of the sensing element. Lifespans are approximately five years and alarms need testing on installation and at least annually with a test gas.

Due to the large power demand of this sensor, it is usually powered from the mains. A battery-powered, pulsed sensor is available with a lifetime of months.

This technology is widely used in Japan and elsewhere in the Far East, with some market penetration in the USA. However, the superior performance of electrochemical cell technology is beginning to displace this technology.

Concentration readout

Although all home detectors use an audible alarm signal as the primary indicator, some versions also offer a digital readout of the CO concentration, in parts per million (PPM). Typically, they can display both the current reading and a peak reading from memory of the highest level measured over some time. These advanced models cost somewhat more but are otherwise similar to the basic models.

The models with display have the advantages of indicating levels below the alarm threshold, reporting levels that may have occurred during an absence, and assessing the degree of hazard if the alarm sounds. They may also aid emergency responders in evaluating the level of past or ongoing exposure or danger.

Portable

Portable detectors are designed for aircraft, cars and trucks. They warn vehicle occupants of any CO hazard.

CO measurement instruments

Portable meters which display CO concentration down to a few PPM are more sensitive than home safety CO detectors and correspondingly much more expensive. They are used by industrial hygienists and first responders, and for maintenance and tracing a CO leak. These devices measure low levels of CO in seconds, rather than minutes or hours like residential alarms. Like other test equipment, professional CO meters must be tested and recalibrated periodically.

Legislation

United States

In the US (As of January 2017) 32 states have enacted statutes regarding carbon monoxide detectors, and another 11 have promulgated regulations on CO detectors,[14] as well as in Washington DC and New York City. In Canada, CO alarm requirements came into effect on October 15, 2014 in Ontario,[15] there is a strong movement in Alberta to make CO detectors mandatory in all homes.[16]

More and more states are legislating for their installation as a mandatory feature.[17]

House builders in Colorado are required to install carbon monoxide detectors in new homes by a bill signed into law in March 2009. House Bill 1091 requires the installation of the detectors in new and resold homes near bedrooms as well as rented apartments and homes. It took effect on July 1, 2009. The legislation was introduced after the death of Denver investment banker Parker Lofgren and his family. Lofgren, along with his wife and children were found dead in their home near Aspen, Colorado on Nov. 27, 2008, victims of carbon-monoxide poisoning.

In New York State "Amanda's Law" (A6093A/C.367) requires one- and two-family residences that have fuel-burning appliances to have at least one carbon monoxide alarm installed on the lowest story having a sleeping area, effective February 22, 2010. Although homes built before January 1, 2008 are allowed to have battery-powered alarms, homes built after that date must have hard-wired alarms. In addition, New York State contractors must install a carbon monoxide detector when replacing a fuel-burning water heater or furnace if the home is without an alarm. The law is named for Amanda Hansen, a teenager who died from carbon monoxide poisoning from a defective boiler while at a sleepover at a friend's house.[18][19]

Alaska House Bill 351 [when?] requires a carbon monoxide detector to be installed in dwelling units that contain or are serviced by a carbon-based fuel appliance or other device that produces by-products of combustion.

In July 2011, California required the installation of carbon monoxide detectors in existing single-family homes, with multifamily homes following in 2013.[20] CA Law 2015 require all new installation of smoke and CO alarms to be 10-year non-serviceable type.[21] Existing alarms may not need to be replaced for homeowners, see local codes. Required alarm locations also vary per local enforcing agencies. In Maine all rental units must have carbon monoxide detectors. In nonrental homes they are recommended but not required. [22]

Standards

North America

The Canadian Mortgage and Housing Association reports, "The standards organizations of Canada (CSA) and the United States (Underwriters Laboratories or UL) have coordinated the writing of CO standards and product testing. The standards as of 2010 prohibit showing CO levels of less than 30 PPM on digital displays. The most recent standards also require the alarm to sound at higher levels of CO than with previous editions of the standard. The reasoning behind these changes is to reduce calls to fire stations, utilities and emergency response teams when the levels of CO are not life threatening. This change will also reduce the number of calls to these agencies due to detector inaccuracy or the presence of other gases. Consequently, new alarms will not sound at CO concentrations up to 70 PPM. Note that these concentrations are significantly in excess of the Canadian health guidelines,"[23] (and also in excess of US Occupational Safety and Health Administration (OSHA) Permissible exposure limits, which is 50 PPM).[24]

References

  1. ^ "Standard for Single and Multiple Station Carbon Monoxide Alarms". UL. Retrieved 2017-10-22.
  2. ^ "UL Mobile | News". Archived from the original on 2016-03-06. Retrieved 2016-02-28.
  3. ^ NFPA 720: Standard for the Installation of Household Carbon Monoxide (CO) Warning Equipment, 2005 Edition, Annex B Dangers of Carbon Monoxide, B.1 Carbon Monoxide, Table B.1 Symptoms of Carbon Monoxide Exposure Based on Concentration
  4. ^ "Consumer Reports buying guide for smoke, carbon monoxide detectors".
  5. ^ "Carbon Monoxide Detectors Buying Guide". ranky10.com. 2017-09-22. Retrieved 2017-10-22.
  6. ^ U.S. Consumer Product Safety Commission, Carbon Monoxide Detectors Can Save Lives (CPSC Document #5010), archived from the original on 2009-04-09, retrieved 2007-07-29
  7. ^ Sorenson, Ida (2022-04-16). "9 Reasons Why Your Carbon Monoxide Detector Went Off Then Stopped". Retrieved 2022-10-14.
  8. ^ NFPA 720: Standard for the Installation of Household Carbon Monoxide (CO) Warning Equipment, 2005 Edition
  9. ^ "Top 5 Things to Know About CO," LifeSafety magazine, Fall 2006
  10. ^ a b Hope, Paul (14 March 2017). "3 Carbon Monoxide Alarms Named 'Don't Buy: Safety Risk' by Consumer Reports". Consumer Reports.
  11. ^ Otieno, Tyron (30 October 2023). "15 Reasons Why Carbon Monoxide Detector Flashing Red But No Sound". Home Safety Point.
  12. ^ Guide to Prevent Carbon Monoxide Poisoning, retrieved 2007-07-29
  13. ^ Gundel, Lara A.; Michael G. Apte; Albert R. Nematollahi (1998). Carbon Monoxide Detector Technology Comparison: Response to Various Gases (PDF) (Technical report). Ernest Orlando Lawrence Berkeley National Laboratory. LBNL-40556. Retrieved 2014-01-14.
  14. ^ "Carbon Monoxide Detector Requirements, Laws and Regulations". National Conference of State Legislatures. 2017-04-03. Retrieved 2017-10-22.
  15. ^ "Carbon Monoxide Alarm Questions and Answers". Ministry of Community Safety and Correctional Services. Archived from the original on October 23, 2017. Retrieved 2017-10-22.
  16. ^ Eva Ferguson (2017-01-06). "Carbon monoxide safety advocate to lobby Alberta to make detectors mandatory in Alberta". Calgary Sun. Archived from the original on 2017-10-24. Retrieved 2017-10-22.
  17. ^ http://artclesgalore.com/article.php?id=2879[permanent dead link]
  18. ^ "Carbon Monoxide Virtual Toolbox". Division of Homeland Security and Emergency Services. 7 November 2014.
  19. ^ "Welcome Page". New York State Office of Fire Prevention & Control. Archived from the original on 2010-05-21.
  20. ^ Senate Bill 183
  21. ^ Updated Smoke Alarm Requirement (Report). 12 February 2015. California State Fire Marshal Information Bulletin 14-006. Archived (PDF) from the original on 2016-05-06.
  22. ^ Carbon Monoxide Environmental & Occupational Health Programs.
  23. ^ Canadian Mortgage and Housing Association Archived April 11, 2013, at the Wayback Machine
  24. ^ "Carbon monoxide". Centers for Disease Control and Prevention (CDC). April 11, 2016. Retrieved May 10, 2016.

Read other articles:

Maraton ChicagoLetakChicago, Illinois, Amerika SerikatJarakMaraton Maraton Chicago (bahasa Inggris: Chicago Marathon) adalah maraton (perlombaan lari jarak jauh) yang diadakan setiap bulan Oktober di Chicago, Illinois. Ini adalah salah satu dari enam perlombaan Marathon Besar Dunia.[1] Dengan demikian, maraton ini juga merupakan perlombaan Label Emas IAAF. Maraton Chicago adalah perlombaan maraton terbesar keempat menurut jumlah pelari di seluruh dunia.[2] Maraton Chicago ...

 

BoundariesPoster rilis teatrikalSutradaraShana FesteProduser Brian Kavanaugh-Jones Chris Ferguson Ditulis olehShana FestePemeran Vera Farmiga Christopher Plummer Lewis MacDougall Bobby Cannavale Kristen Schaal Christopher Lloyd Peter Fonda Penata musikMichael PennSinematograferSara MisharaPenyunting Marie-Hélène Dozo Dorian Harris Perusahaanproduksi Automatik Entertainment Oddfellows Entertainment Stage 6 Films Distributor Sony Pictures Classics Mongrel Media Tanggal rilis 12 Maret 20...

 

Arifin Noor Wakil Wali Kota Banjarmasin ke-4PetahanaMulai menjabat 23 Juni 2021PresidenJoko WidodoGubernurSafrizal ZA (Pj.) Sahbirin NoorWali KotaIbnu Sina PendahuluHermansyahPenggantiPetahana Informasi pribadiLahir22 Agustus 1960 (umur 63)Kandangan, Kalimantan SelatanPartai politikPKBSuami/istriHardiyanti, S.Sos.Anak4Alma materUniversitas Lambung MangkuratInstitut Teknologi Sepuluh NopemberUniversitas 17 Agustus 1945 SurabayaPekerjaanBirokratPolitikusSunting kotak info • ...

Dewan Perwakilan Rakyat DaerahProvinsi GorontaloPeriode 2019-2024JenisJenisUnikameral SejarahSesi baru dimulai9 September 2019PimpinanKetuaParis R.A. Jusuf (Golkar) sejak 30 September 2019 Wakil Ketua IMoh. Kris Wartabone (PDI-P) sejak 30 September 2019 Wakil Ketua IISofyan Puhi (NasDem) sejak 30 September 2019 Wakil Ketua IIIAwaludin Pauweni (PPP) sejak 30 September 2019 KomposisiAnggota45Partai & kursiPemerintah (38)   PKB (1)   Partai Gerindra (4) &#...

 

Teman BusDidirikan2 Juni 2020Lokal Sumatera Utara Sumatera Selatan Jawa Barat Jawa Tengah Daerah Istimewa Yogyakarta Jawa Timur Bali Kalimantan Selatan Sulawesi Selatan Wilayah layananIndonesiaJenis layananAngkutan cepat busRuteLihat di bawahOperatorKementerian Perhubungan RI dan masing-masing operator angkutan cepat busSitus webtemanbus.com Teman Bus (singkatan dari Transportasi Ekonomis Mudah Aman dan Nyaman) adalah sistem transportasi angkutan cepat bus (bus rapid transit/BRT) di Indonesia...

 

Об экономическом термине см. Первородный грех (экономика). ХристианствоБиблия Ветхий Завет Новый Завет Евангелие Десять заповедей Нагорная проповедь Апокрифы Бог, Троица Бог Отец Иисус Христос Святой Дух История христианства Апостолы Хронология христианства Ран�...

Basilika Bunda Maria dari El Valle, El Valle del Espíritu Santo. Ini adalah daftar lengkap Basilika di Venezuela. Basilika adalah gelar yang diberikan kepada beberapa gereja Katolik. Berdasarkan hukum kanonik tidak ada gereja Katolik yang dapat dihormati dengan gelar basilika kecuali mendapatkan hibah apostolik atau berdasarkan kebiasaan dahulu kala.[1] Gelar ini diberikan kepada gereja-gereja besar yang penting sebagai tempat ziarah atau untuk pengabdian tertentu seperti kepada oran...

 

What Yo Name Iz?Single by Kirko Bangzfrom the album Procrastination Kills 3 ReleasedFebruary 7, 2011 (2011-02-07)[1]Recorded2010GenreHip hopLength3:25LabelWarner Bros. RecordsSongwriter(s)Kirk RandleRaul GonzalezBrandon TillmanProducer(s)Sound M.O.B.[2]Kirko Bangz singles chronology What Yo Name Iz? (2011) Drank in My Cup (2011) What Yo Name Iz? is the debut single by American rapper Kirko Bangz. The Sound M.O.B. produced song was featured on his mixtape Pro...

 

Radio station in Julesburg, ColoradoKJBLJulesburg, ColoradoBroadcast areaNortheastern Colorado and Panhandle area of NebraskaFrequency96.5 MHzProgrammingFormatClassic hitsOwnershipOwnerArmada Media - MccookSister stationsKHAQ, KXNP, KODY, KMTY, KUVR, KADL, KICX, KQHK, KBRL, KFNF, KSTH,HistoryFirst air dateFebruary 2, 1999 (as KEGK)Former call signsKEGK (1999-2001)KKAS (2001-2004)KKYT (2004-2005)Technical informationFacility ID84864ClassAERP265 wattsHAAT-32.4 metersTransmitter coordinates40°5...

Division 2 1973-1974 Competizione Ligue 2 Sport Calcio Edizione 35ª Organizzatore LFP Luogo  Francia Partecipanti 36 Risultati Vincitore  Lilla Promozioni  Lilla Red Star Paris Saint-Germain Retrocessioni  Poitiers Le Mans La Rochelle JGA Nevers Arles CS Vittel Statistiche Miglior marcatore Erwin Wilczek Nestor Combin Incontri disputati 612 Gol segnati 1 700 (2,78 per incontro) Cronologia della competizione 1972-1973 1974-1975 Manu...

 

Overview of marine occupations This article has multiple issues. Please help improve it or discuss these issues on the talk page. (Learn how and when to remove these template messages) This article needs additional citations for verification. Please help improve this article by adding citations to reliable sources. Unsourced material may be challenged and removed.Find sources: Seafarer's professions and ranks – news · newspapers · books · scholar · JST...

 

NefertariPermaisuri MesirIstri Kerajaan AgungNyonya Dua TanahNyonya Mesir Atas dan Bawah, dllDinding makam yang menggambarkan Ratu Nefertari, istri kerajaan Firaun Ramses IIKematianskt. 1255 SMPemakamanmakam QV66, Lembah Ratu, ThebesNama lengkapNefertari MeritmutPasanganRamses IIAnakAmun-her-khepeshefPareherwenemefMeryatumMeryreMeritamenHenuttawyBaketmut (mungkin)Nefertari (mungkin)Nebettawy (mungkin)AgamaAgama Mesir Kuno Nefertari Meritmut Era: Kerajaan Baru(1550–1069 BC) Hieroglif Me...

The Center of the WorldPoster resmiSutradaraWayne WangProduserWayne Wang Peter NewmanDitulis olehWayne Wang Miranda July Paul Auster Siri HustvedtPemeranPeter Sarsgaard Molly Parker Carla GuginoSinematograferMauro FiorePenyuntingLee PercyPerusahaanproduksiRedeemable FeaturesDistributorArtisan EntertainmentTanggal rilis 19 April 2001 (2001-04-19) Durasi88 menitNegaraAmerika SerikatBahasaInggris The Center of the World adalah sebuah film drama Amerika Serikat tahun 2001 yang disutradarai o...

 

Grand Prix Britania 1991 Lomba ke-8 dari 17 dalam Formula Satu musim 1991 Detail perlombaanTanggal 14 July 1991Nama resmi XLIV Foster's British Grand PrixLokasi Silverstone CircuitSilverstone, United KingdomSirkuit Permanent racing facilityPanjang sirkuit 4.778 km (2.969 mi)Jarak tempuh 59 putaran, 308.334 km (188.446 mi)Cuaca Hot, dry, sunnyPosisi polePembalap Nigel Mansell Williams-RenaultWaktu 1:20.939Putaran tercepatPembalap Nigel Mansell Williams-RenaultWaktu 1:26.379 putaran ke-43Podium...

 

1983 Labour Party leadership election ← 1980 2 October 1983 (1983-10-02) 1988 →   Candidate Neil Kinnock Roy Hattersley Overall result 71.3% 19.3% Affiliated unions 72.6% 27.2% Party members 91.5% 1.9% Labour MPs 49.3% 26.1%   Candidate Eric Heffer Peter Shore Overall result 6.3% 3.1% Affiliated unions 0.1% 0.1% Party members 6.6% — Labour MPs 14.3% 10.3% Leader before election Michael Foot Elected Leader Neil Kinnock The 1...

Phase contrast magnetic resonance imagingVastly undersampled Isotropic Projection Reconstruction (VIPR) of a phase contrast (PC) MRI sequence of a 56-year-old male with dissections of the celiac artery (upper) and the superior mesenteric artery (lower). Laminar flow is present in the true lumen (closed arrow) and helical flow is present in the false lumen (open arrow).[1]Purposemethod of magnetic resonance angiograph Phase contrast magnetic resonance imaging (PC-MRI) is a specific typ...

 

Prescott F. Hall, one of the founders of the Immigration Restriction League The Immigration Restriction League was an American nativist and anti-immigration organization founded by Charles Warren, Robert DeCourcy Ward, and Prescott F. Hall in 1894. According to Erika Lee, in 1894 the old stock Yankee upper-class founders of the League were, convinced that Anglo-Saxon traditions, peoples, and culture were being drowned in a flood of racially inferior foreigners from Southern and Eastern Europe...

 

Location of the Alligator Alley Reservation in Broward County The Miccosukee Indian Reservation is the homeland of the Miccosukee tribe of Native Americans. It is divided into three sections in two counties of southern Florida, United States. Their total land area is 128.256 sq mi (332.18 km2). The Miccosukee Reservation have members living on and off the reservation. The largest section by far is known as the Alligator Alley Reservation, which is located at the extreme western...

Irish League 1908-1909 Competizione Irish League Sport Calcio Edizione 19ª Luogo Irlanda Formula Girone all'italiana Cronologia della competizione 1907-08 1909-10 Manuale Il campionato era formato da otto squadre e il Linfield vinse il titolo. Non vi furono retrocessioni. Classifica finale Pos. Squadra G V N P GF GS Punti 1 Linfield 14 10 1 3 27 13 21 2 Glentoran 14 8 3 3 29 22 19 3 Shelbourne 14 7 0 7 20 20 14 4 Distillery 14 6 1 7 22 19 13 = Bohemians 12 6 1 5 27 24 13 6 Belfast Celtic 13...

 

У этого термина существуют и другие значения, см. Черкассы (значения). Не следует путать с Черкасском. ГородЧеркассыукр. Черкаси Флаг Герб 49°26′40″ с. ш. 32°03′35″ в. д.HGЯO Страна  Украина Статус областной центр Область Черкасская область Район Черкасский район О�...